				Alarm on panel being caused by bad pull and Module. Recommend replacing (1) PS-DALOB and (1) SK-Minimod. Wired through pull M33 M1 and deleted from programming until replacement is made. Supervisory on panel for Module 4. This is monitoring troubles for power supply to the right of FACP. Found that there was a battery trouble and an output 4 trouble. Replaced (2) 12v8ah batteries for power supply from truck 134 stock. Located output 4 trouble on second floor in unit under construction. Contractors removed speaker. Re-mounted speaker and cleared trouble. Clearing these issues removed the supervisory. System back online in normal condition.
 
				Perform annual fire alarm and fire extinguisher inspection for commercial customer. Ensure that property has enough fire exstinguishers for their space and that they are evenly distributed. Checked that all systems are functional, tagged and adequately charged.
 
				Although it is not required by NFPA code, we recognize there are several instances when you want to make sure your single-family fire sprinkler system is going to function when you need it most! We choose to be ahead of the curve on the safety, confidence and functionality inspections and therefore offer this comprehensive system evaluation to offer you peace of mind that your life and the lives of those in your home are as safe as possible in the event of a fire emergency! We will provide a visual inspection of all accessible fire sprinkler system devices and a report of the systems overall health. Northwest Fire System will provide visual inspection on the following accessible devices: System Controls and Signage Sprinklers and Trim Piping and Insulation (if visible through crawlspace or attic access) Hangers and Bracing (if visible through crawlspace or attic access) Notification and Alarms (if applicable) Standard Exclusions: Washington State Sales Tax Any repairs needed or desi